Hotline 1 : 0812-8927-0182 Hotline 2 : 02122278639 (Office Hour) Whatsapp : 0812-9407-7633
IMG-LOGO

LNK-AI Analog Input Peripheral Device

CETCII Critical Instrument

Category : Remotes & Peripherals

Kondisi : NEW

View : 129

ORDER NOW !!
Hotline 1 : 0812-8927-0182
Hotline 2 : 02122278639 (Office Hour)
Whatsapp : 0812-9407-7633

The LNK-AI Analog Input peripheral device adds four channels of 4 - 20 mA or 0 - 10 volt analog inputs to a Modbus® network configured with an FCS Flexible Control System Controller. The LNK-AI is designed to receive an analog signal from one to four transmitters and communicates back to the FSC using Modbus® RS-485. The FCS monitors the connection and will indicate a loss of communications. Ideal for large applications to create an efficient distribution network of specialized gas detection devices with fewer wires running directly from the controller.

Key Features

  • Four 4-20 mA input channels
  • Power LED indicator
  • Modbus® RS-485 RTU communication
  • Scaling and zoning capabilities supported by the ontroller
  • Configurable default settings for any interruption in communication
  • Standard water / dust tight, corrosion resistant enclosure

Specifications

Mechanical

Enclosure

ABS / Polycarbonate, corrosion resistant

Copper coated interior to reduce RF interference

Weight

400 g / 14 oz

Size

127 x 127 x 71 mm / 5.0 x 5.0 x 2.8 inches

User Interface

Indicator

LED green indicator for power

Input/Output

Output

Four 4-20 m A (2 - 10 volts is obtainable using a 500 Ohm resistor)

Communication

Modbus® RS-485 RTU

Electrical

Power Requirement

24 VDC, 1W, Class 2 (24 VDC supplied by the Controller)

Wiring

4-conductor shielded minimum 18 AWG stranded within conduit

Fuses

Thermal, resetting

Environmental

Operating Temperature

-20°C to 40°C (-4°F to 104°F)

Operating Humidity

15 - 90% RH non-condensing

Certifications

Conforms to:

CSA-C22.2 No. 205-12, UL508 (Edition 17):2007

EMC Directive 2004/108/EC, EN 50270:2006, Type 1, EN61010

FCC. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

RoHS compliant circuit boards