Hotline 1 : 0812-8927-0182 Hotline 2 : 02122278639 (Office Hour) Whatsapp : 0812-9407-7633
IMG-LOGO

LPT-B BACnet® Transmitter

CETCII Critical Instrument

Category : Gas Detectors

Kondisi : NEW

View : 129

ORDER NOW !!
Hotline 1 : 0812-8927-0182
Hotline 2 : 02122278639 (Office Hour)
Whatsapp : 0812-9407-7633

The LPT-B is a full featured, 3 channel, BACnet® transmitter for use in non-hazardous, non-explosion rated, commercial and light industrial applications. It is available with a wide range of internal and/or external sensors and sensor types including electrochemical, catalytic and PID TVOCs. The LPT-B may be configured to operate as a standalone fixed system or be part of a digital network. It offers a BACnet® MS/TP output signal for communicating with a Controller or Building Automation System, an audible internal alarm, one SPDT dry contact relay, LCD display with user selectable functions, temperature compensation and thermal resetting fuses all in a RoHS compliant package. The LPT-B comes in a standard water / dust tight, corrosion resistant ABS / polycarbonate enclosure with a hinged, secured door. It is IP54 rated with the optional splash guard installed which provides protection in water spray or wash down applications. The LPT-B is not compatible with CETCI’s Controllers. It is intended to be used alone or integrated into an existing BACnet® network.

Key Features

  • 1, 2 or 3 channel operation with internal and/or remote sensor configurations
  • BACnet® MS/TP communication
  • LCD display
  • One 2A SPDT dry contact relay
  • Internal audible alarm
  • 24 VAC/VDC power
  • 4-conductor daisy chain network wiring
  • Unobtrusive calibration and menu navigation using a magnetic wand
  • Standard water / dust tight, corrosion resistant enclosure (drip proof)
  • IP54 rated with optional splash guard installed.

Specifications

Target Gas

Electrochemical Sensors (internal)

Ammonia (NH3), Carbon monoxide, Chlorine (Cl2), Chlorine dioxide (ClO2), Ethylene (C2H4), Ethylene oxide (C2H4O), Fluorine (F2), Formaldehyde (CH2O), Hydrogen (H2), Hydrogen chloride (HCl), Hydrogen cyanide (HCN), Hydrogen fluoride (HF), Hydrogen sulphide (H2S), Nitric oxide (NO), Nitrogen dioxide (NO2), Oxygen (O2), Ozone (O3), Phosphine (PH3), Silane (SiH4), Sulphur dioxide (SO2), TVOCs (Isobutylene)

Catalytic Sensors (remote)

Hydrogen (H2), Methane (CH4), Propane (C3H8)

PID Sensors (remote)

TVOCs

Infrared Sensors (remote)

Propane (C3H8)

Mechanical

Enclosure

ABS / Polycarbonate, corrosion resistant

Copper coated interior to reduce RF interference

IP54 rated with optional splash guard installed

Weight

363 g / 0.80 lbs

Size

127 x 127 x 71 mm / 5.0 x 5.0 x 2.8 inches

User Interface

Display

Graphic LCD, yellow border

Magnetic switches to initiate calibration without opening the enclosure

Input/Output

Output

BACnet® MS/TP communications

Relay

One SPDT dry contact, rated at 30 volts, 2 amps max

Audible Alarm

Standard internal buzzer

Electrical

Power Requirement

16-30 VDC, 3 W, Class 2

12-27 VAC, 50-60 Hz, 3 VA, Class 2

Current Draw

55 mA (buzzer & relay energized, 2 sensors)

Wiring

4-conductor, 16 AWG stranded, shielded network wiring (daisy-chain)

Fuses

Thermal, resetting

Environmental

Operating Temperature

-20°C to 40°C (-4°F to 104°F)

Operating Humidity

15 - 90% RH non-condensing

Certifications

Conforms to

CSA-C22.2 No. 205-12 / UL508 (Edition 17):2007

EMC Directive 2004/108/EC, EN 50270:2006, Type 1, EN61010

FCC. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

Listed by BTL

RoHS compliant circuit boards