Input/Output
Audible Alarm
Standard loud, door mounted buzzer, rated 90 dB @ 30 cm (1 ft)
Optional: door mounted, water tight buzzer, rated 85 dB @ 60.96 cm (2 ft)
Top Mounted Strobe
Optional: bright, red, top mounted 24 V strobe, 7 cm dia x 12.7 cm H / 2.75” dia x 5” H
Electrical
Power Requirement
Line Voltage: 90 – 240 VAC, 50 -60 Hz, 75 W
Current Draw
Line Voltage (110 VAC): approx. 1.0 amps
Line Voltage (220 VAC): approx. 0.5 amps
Power Distribution
Total power available for Remote & Peripheral Devices and Options 65 W @ 24 VDC
Wiring
Line Voltage: VAC 3-conductor shielded minimum 18 AWG stranded within conduit
LAN Modbus® RTU (version 1.1b3) RS-485, 16 gauge, 4-conductor shielded
WAN (output to BAS only): Modbus® RS-485 or BACnet® MS/TP, 4-conductor shielded
Fuses
Thermal, resetting
Environmental
Operating Temperature
-20°C to 40°C (-4°F to 104°F)
Operating Humidity
15 - 90% RH non-condensing
Certifications
Conforms to:
CSA-C22.2 No. 205-12, UL508 (Edition 17):2007
EMC Directive 2004/108/EC, EN 50270:2006, Type 1, EN61010
FCC. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
FCS-B, FCS-B-X models are Listed by BTL (where X represents one or more factory installed Options)
RoHS compliant circuit boards