Hotline 1 : 0812-8927-0182 Hotline 2 : 02122278639 (Office Hour) Whatsapp : 0812-9407-7633
IMG-LOGO

FCS Flexible Control System ( up to 128 Channels)

CETCII Critical Instrument

Category : Controllers

Kondisi : NEW

View : 129

ORDER NOW !!
Hotline 1 : 0812-8927-0182
Hotline 2 : 02122278639 (Office Hour)
Whatsapp : 0812-9407-7633

The FCS Flexible Control System is a sophisticated, high performance controller that offers up to 128 gas channel configurations for monitoring toxic, combustible or refrigerant gases with versatile control functionality for non-hazardous, non-explosion rated, commercial and light industrial applications. The FCS is designed to accept inputs from digital, analog and wireless transmitters and/or Peripheral Devices (in various combinations), using Modbus® RS-485,  4-20 mA analog input or wireless communication. The FCS is available in two models: the FCS-M with Modbus® RS-485 output or the FCS-B with BACnet® MS/TP output for communicating with a Building Automation System (BAS). Standard features include, four configurable SPDT dry contact relays with field configurable time delays and trigger levels, a full colour LCD touch screen with LED panel indicating configurable channel alarm status, relay status and fault conditions, extensive menu system with password protection, enhanced logic control, priorities/zoning capabilities, a USB port for firmware upgrades, data logging and a door-mounted, audible alarm. Optional value added features include, analog inputs and/or analog outputs, a top mounted strobe, a locking door and a water tight, door-mounted audible alarm. The FCS can can be connected to several remote devices such as a remote strobe & horn, a Remote Display Module and several LNK Peripheral Devices. It can also be configured to comply with California Title-24 Building Energy Efficiency Standards. (Specification details need to be given at time of order and additional settings can be implemented in the field as required.)

Key Features

  • Up to 128 channels of gas readings
  • FCS-M offers Modbus® RS-485 digital output signal for LAN and WAN communications
  • FCS-B offers BACnet® MS/TP output signal for WAN communications (for communicating with a BAS)
  • Graphic, full colour, resistive rouch LCD screen with LED indicators
  • 4 dry contact relays, 5-amps @240 volts each
  • Line Voltage (90-240 VAC)
  • USB port for firmware upgrades and data logging
  • Configurable to comply with California Title-24 Energy Efficiency Standards
  • Door mounted audible alarm, optional water tight version available
  • Optional internal analog inputs and/or analog outputs
  • Standard water / dust tight, corrosion resistant enclosure (drip proof); IP54 rated with water tight, door mounted audible alarm installed

 

Specifications

Input/Output

Audible Alarm

Standard loud, door mounted buzzer, rated 90 dB @ 30 cm (1 ft)

Optional: door mounted, water tight buzzer, rated 85 dB @ 60.96 cm (2 ft)

Top Mounted Strobe

Optional: bright, red, top mounted 24 V strobe, 7 cm dia x 12.7 cm H / 2.75” dia x 5” H

Electrical

Power Requirement

Line Voltage: 90 – 240 VAC, 50 -60 Hz, 75 W

Current Draw

Line Voltage (110 VAC): approx. 1.0 amps

Line Voltage (220 VAC): approx. 0.5 amps

Power Distribution

Total power available for Remote & Peripheral Devices and Options 65 W @ 24 VDC

Wiring

Line Voltage: VAC 3-conductor shielded minimum 18 AWG stranded within conduit

LAN Modbus® RTU (version 1.1b3) RS-485, 16 gauge, 4-conductor shielded

WAN (output to BAS only): Modbus® RS-485 or BACnet® MS/TP, 4-conductor shielded

Fuses

Thermal, resetting

Environmental

Operating Temperature

-20°C to 40°C (-4°F to 104°F)

Operating Humidity

15 - 90% RH non-condensing

Certifications

Conforms to:

CSA-C22.2 No. 205-12, UL508 (Edition 17):2007

EMC Directive 2004/108/EC, EN 50270:2006, Type 1, EN61010

FCC. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

FCS-B, FCS-B-X models are Listed by BTL (where X represents one or more factory installed Options)

RoHS compliant circuit boards